TelcoSafe® LIST 2

Central Office Power Wire and Cable

Limited Smoke, Non-Halogenated Insulated, Silicone-Free, Lead-Free
Meets European RoHS directive
90°C Dry, 75°C Wet – 600 Volts DC or AC
UL Listed RHH/RHW/ST1 and VW-1 (8 AWG and Larger)
UL Listed “For CT Use” (1/0 AWG and Larger)
CSA Listed AWM I A/B, 105°C, 1000 Volts, FT1, FT2
FT4-ST1, -40°C, W75C
Audited by Telcordia to all 33 requirements of GR-347-CORE
Meets IEC including 60674 & 60332

WARNING: California Proposition 65 – Cancer and Reproductive Harm.
www.P65Warnings.ca.gov
 

Scope

This specification covers the construction requirements for limited smoke,
non-halogenated Central Office Power Wire and Cable, insulated with a
proprietary EVA Copolymer limited smoke, non-halogenated compound. UL
listed Type RHH/RHW/ST1, for use in accordance with the National Electrical
Code.
The construction of the wire and cable is in accordance with Underwriters’
Laboratories requirements and the requirements of CSA for the FT4/ST1
flame/smoke test. Sizes 1/0 AWG and larger are UL “CT Use” (Cable Tray)
rated.

Construction

Size (AWG OR KCMIL) & Part # Stranding Conductor Diameter (Inches) Insulation Min. Avg. Wall (mils) Nominal Insulation Diam. (Inches)
8-V158120 41 .153 60 .28
6-V158122 65 .188 60 .315
4-V158124 126 .26 60 .385
2-V158127 168 .305 60 .43
1/0-V158131 266 .392 80 .56
2/0-V158132 342 .455 80 .62
4/0-V158136 532 .577 80 .745
350-V158140 888 .76 95 .96
500-V158142 1221 .89 95 1.09
750-V158148 1850 1.094 110 1.32

Size: 8 AWG Through 750 KCMIL – Single Conductor

Conductors:Flexible bunch or rope-lay stranded, tin-coated copper conforming to ASTM B-
33, B-172, or B-174 and Underwriters’ Laboratories requirements. An opaque
Mylar tape shall be applied over the conductor to facilitate stripping.

Insulation: Black EVA Copolymer limited smoke, non-halogen, lead-free compound conforming to Underwriters’ Laboratories Standard 44, Subjects 509 and 758, and CSA C22.2 No. 210-2-M90.  The insulation has a limiting oxygen index (L.O.I.) minimum of 28%.  Other colors can be furnished upon request.

Surface Marking:Two sides of the cable shall be printed using an ink of contrasting color and
with the following information:

“SOUTHWIRE AIW™ CORD BRAND TELCOSAFE® L1 NON-HAL (UL) E18321
SIZE AWG 600 VOLTS RHH OR RHW/ST/1 FT4/IEEE1202 SR — LL90458 CSA
AWM I A/B 105°C 1000 VOLTS W75C -40°C FT1, FT2, FT4-ST1 (YEAR of MFG)
— MEETS IEC INCLUDING 60674 & 60332 — (SEQ. FOOTAGE. ON 1 SIDE)”

For Sizes 1/0 AWG and larger add, “FOR CT USE” before “(UL)”
For Sizes 8 AWG and larger add, “VW-1” after “(UL)”

Testing: Physical and electrical tests in accordance with the requirements of UL Standard 44, Subject 509 and 758, and CSA Standard C22.2 No. 210.2-M90 as AWM.

Labels: UL and CSA tags and labels shall be applied to all packages.

Lengths: All put-ups one length only unless agreed to otherwise. Maximum lengths per size will be advised.

Packaging: The ends of the cable shall be capped or taped to prevent the entrance of moisture during shipment or storage.

Rail and Transit

Exane®1093
Exane® TFE Fluoropolymer
Exane®Transit 600V
2KV-DLO
Exane® 1068A-600V
Exane® 1068A-2000V
Exane®-1069A
Exane®-15 1168B Multi-Conductor 600V
Exane® Case Wire
Exane® 15 Reduced Dia. 600V
Exane® ZH-1105A 600V
Exane®ZH-1105A 2000V
Exane®ZH-1105A 600/1000V Metric
Exane®ZH-1105A 1800/3000V Metric
Exane®ZH-1105A 1800V/3000V Metric
1KV-DLO

Telecommunications

TelcoSafe® LIST 1
TelcoSafe® LIST 2
Intra-Bay Wiring
TelcoFlex® II
TelcoFlex® III
TelcoFlex® IV

Data

Exane® RS-485
Exane® CAT 6 4 Pairs 24 AWG
Exane®Cat 5E 4 Pairs 24 AWG
Exane® CAT 5E 2 Pairs 22 AWG
Exane® MVB/WTB 4C 20 AWG
Exane® MVB/WTB 2C 20 AWG

Exane Compliance Certification

Download this Sheet as a PDF

Adobe Reader required.