TelcoSafe® 13949 I

Central Office Power Wire and Cable

Limited Smoke, Non-Halogenated Insulated, Silicone-Free
Meets European RoHS directive
90°C Dry, 75°C Wet – 600 Volts
UL Listed RHH/RHW/ST1 and VW-1 (8 AWG and Larger)
UL Listed “For CT Use” (1/0 AWG and Larger)
CSA Listed AWM I A/B, 105°C, 1000 Volts, FT1, FT2
FT4-ST1, -40°C, W75C
Complies with Telcordia GR-347-CORE

Scope

This specification covers the construction requirements for limited smoke, non-halogenated Central Office Power Wire and Cable, insulated with a proprietary EVA Copolymer limited smoke, non-halogenated compound.  UL listed Type RHH/RHW/ST1, for use in accordance with the National Electrical Code.

The construction of the wire and cable is in accordance with Underwriters’ Laboratories requirements and the requirements of CSA for the FT4/ST1 flame/smoke test.  Sizes 1/0 AWG and larger are UL “CT Use” (Cable Tray) rated.

Construction

Size (AWG OR KCMIL) Stranding Conductor Diameter (Inches) Insulation Min. Avg. Wall (mils) Nominal Insulation Diam. (Inches) Max D.C. Res. @ 20°C (OHMS Per 1000 Feet) Ampacity Per Nec Table 310.16
75°C 90°C
14 7/.0242” .071 45 .165 2.62 20 25
12 7/.0305” .090 45 .185 1.65 25 30
10 7/.0385” .114 45 .210 1.03 35 40
8 7/.0486” .143 60 .270 .653 50 55
6 7/.0612” .180 60 .305 .411 65 75
4 7/.0772” .227 60 .350 .258 85 95
2 7/.0974” .286 60 .410 .162 115 130
1 19/.0664” .332 80 .500 .129 130 150
1/0 19/.0745” .365 80 .530 .102 150 170
2/0 19/.0837” .411 80 .575 .081 175 195
3/0 19/.0940” .470 80 .640 .064 200 225
4/0 19/.1055” .517 80 .680 .050 230 260
250 37/.0822” .575 95 .775 .043 255 290
350 37/.0973” .667 95 .860 .030 310 350
500 37/.1162” .797 95 .990 .021 380 430
600 61/.0992” .893 110 1.120 .018 420 475
750 61/.1109” .978 110 1.200 .014 475 535

Size: 14 AWG Through 750 KCMIL – Single Conductor

Conductors: Class B concentric stranded, bare copper conforming to ASTM B-8 and Underwriters’ Laboratories requirements.  An opaque mylar tape shall be applied over the conductor to facilitate stripping.  Tinned copper is available upon request.

Insulation: Gray EVA Copolymer limited smoke, non-halogen, compound conforming to Underwriters’ Laboratories Standard 44, Subjects 509 and 758, and CSA C22.2 No. 210-2-M90.  In addition, the insulation complies with the requirements of TelcordiaTechnologies GR-347-Core.  The insulation has a limiting oxygen index (L.O.I.) minimum of 28%.  Other colors can be furnished upon request.

Surface Marking: Two sides of the cable shall be printed using an ink of contrasting color and with the following information: “TelcoSafe L1 NON-HAL (SIZE) AWG (OR KCMIL) 600V. RHH OR RHW/ST1 FT4/IEEE1202 (UL) E18321 — A.I.W. CORP. — LL 8825 CSA AWM I A/B 105°C 1000V. W75C, -40°C FT1, FT2 FT4-ST1 (YEAR) (SEQ. FTG. ON 1 SIDE)”

For Sizes 1/0 AWG and larger add, “FOR CT USE” before “(UL)”
For Sizes 8 AWG and larger add, “VW-1″ after “(UL)”

Testing: Physical and electrical tests in accordance with the requirements of UL Standard 44, Subject 509 and 758, and CSA Standard C22.2 No. 210.2-M90 as AWM.

Labels: UL and CSA tags and labels shall be applied to all packages.

Lengths: All put-ups one length only unless agreed to otherwise. Maximum lengths per size will be advised.

Packaging: The ends of the cable shall be capped or taped to prevent the entrance of moisture during shipment or storage.

Rail and Transit

Exane® 1068A-2000V
Exane® ZH V15
Exane® 1069A/1093
Exane® 1068A-600V
Exane® 1062
Exane® 15 MCSU 600V
Exane® 15 RD 600V

Telecommunications

TelcoFlex® II
TelcoFlex® III
TelcoFlex® IV
TelcoSafe® 13949 I
TelcoSafe® 13950 E

Central Office

Switchboard 85
Switchboard 100Ohm
T100 Central Office
1249C Central Office
600C Central Office



Download this Sheet as a PDF

Adobe Reader required.