TelcoFlex® IV

<b>Surface Marking:</b> Two sides of the cable shall be printed using an ink of contrasting color and with the following information: "TelcoFlex™ fI/KS24194™ L2 NON-HAL (SIZE) AWG (OR KCMIL) 600V. RHHILS FT4 (UL) OR AWM 3578 VW-1 E18321---A.I.W. CORP.--LL8825 CSA AWM I B 105°C 600V. FT4-ST1 (YEAR) (SEQ. FTG. ON 1 SIDE)". For sizes 1/0 AWG and larger add uFOR CT USE" before "(UL)"  <b>Testing:</b> Physical and electrical tests in accordance with UL Standard 44 requirements.  <br /><b>Labels:</b> UL tags and labels shall be applied to each reel.

Central Office Power Wire and Cable
Class I Flexible Strand With Braid

Low Smoke, Non-Halogenated Insulation With Cotton Braid, Lead-Free and Silicone-Free, UL Listed RHH/LS FT4 and VW-1, 90°C Dry, 60°C Wet, 600 Volts, UL Listed “For CT USE” (1/0 AWG and Larger), CSA AWM I B 105°C, 600 Volts, FT4

Scope

This specification covers the construction requirements for low smoke, non-halogenated, TelcoHyde™ 5221 insulated, cotton braided power wire and cable, type RHH/LS for use in accordance with the National Electrical Code.

The construction of the wire and cable is in accordance with Underwriters’ Laboratories requirements and the requirements of CSA for the FT4 flame tests. Sizes 1/0 AWG and larger are UL “CT USE” rated.

CONSTRUCTION

Size: 8 AWG through 750 KCMIL – Single conductor

Conductors: Class I (modified) bunched (8 and 6 AWG) and rope-bunched (4 AWG and larger) stranded tinned copper conforming to ASTM B-33 and Underwriters’ Laboratories requirements. An opaque mylar tape shall be applied over the conductor to facilitate stripping.

Insulation: 90°C rated limited smoke, non-halogen, TelcoHyde™ 5221 conforming to Underwriters’
Laboratories Standard 44 and Telcordia Specification GR-347-CORE, also CSA 105°C AWM rated. The insulation has a limiting oxygen index of 35%.

Separator: On sizes 6 AWG and larger, a 1 mil clear mylar tape shall be applied over the insulation.

Covering: On all sizes, a natural cotton braid conforming to UL requirements is applied overall. A section of completed cable has a limiting oxygen index of 35%.

Finish: A moisture resistant, fire retardant saturant and a colored finisher is applied to the braid.

Surface Marking: Two sides of the cable shall be printed using an ink of contrasting color and with the following information: “TelcoFlex™ IV/KS24194™ L4 NON-HAL (SIZE) AWG (OR KCMIL) 600V. RHH/LS FT4 (UL) OR AWM 3578 VW-1 E18321—A.I.W. CORP.—LL8825 CSA AWM I B 105°C 600V. FT4 (YEAR) (SEQ. FTG. ON 1 SIDE)”.

For sizes 1/0 AWG and larger add “FOR CT USE” before “(UL)”

Testing: Physical and electrical tests in accordance with UL Standard 44 requirements.

Labels: UL tags and labels shall be applied to each reel.

CABLE DATA

PART NUMBER SIZE AWG OR KCMIL STRANDING CONDUCTOR DIAMETER (INCHES) INSULATION MIN. AVG. WALL (MILS) NOMINAL INSULATION DIAMETER (INCHES) NOMINAL OUTSIDE DIAMETER (INCHES) MAX D.C. RES. @ 20° C (OHMS/M FT.) APPROX WEIGHT LBS./M FT.
39770 8 41/.0201″ .153 60 .280 .330 .6790 86
39771 6 65/.0201″ .188 60 .315 .365 .4360 120
39772 4 105/.0201″ .260 60 .385 .435 .2740 193
39773 2 168/.0201″ .305 60 .430 .480 .1720 284
39774 1/0 266/.0201″ .392 80 .560 .615 .1090 479
39775 2/0 342/.0201″ .455 80 .620 .675 .0868 593
39776 4/0 532/.0201″ .577 80 .745 .800 .0546 882
39777 350 888/.0201″ .760 95 .960 1.015 .0334 1373
39778 500 1221/.0201″ .890 95 1.090 1.145 .0234 1906
39779 750 1850/.0201″ 1.094 110 1.325 1.380 .0157 2792

*Also available in black, blue, green, red and with black tracer; consult factory.

Rail and Transit

Exane® 1068A-2000V
Exane® ZH V15
Exane® 1069A/1093
Exane® 1068A-600V
Exane® 1062
Exane® 15 MCSU 600V
Exane® 15 RD 600V

Telecommunications

TelcoFlex® II
TelcoFlex® III
TelcoFlex® IV
TelcoSafe® 13949 I
TelcoSafe® 13950 E

Central Office

Switchboard 85
Switchboard 100Ohm
T100 Central Office
1249C Central Office
600C Central Office



Download this Sheet as a PDF

Adobe Reader required.